Eclipse
Ratings
|
Rated Normal Current |
A |
630 |
1250 |
2000 |
|
Rated Voltage |
kV |
12 |
12 |
12 |
|
Rated Frequency |
Hz |
50 |
50 |
50 |
|
Rated BIL |
pk kV |
75/95 |
75/95 |
75/95 |
|
Rated Power Frequency Withstand |
kV 1min |
28/38 |
28/38 |
28/38 |
|
Rated Short-Time Withstand Current |
kArms 3secs |
20/25 |
20/25 |
20/25 |
|
Rated Peak Making Current |
pk kA |
50/62.5 |
50/62.5 |
50/62.5 |
|
Internal Arc Compliance |
kA 1sec |
25 |
25 |
25 |
|
Rated Short Circuit Breaking Current |
kA |
20/25 |
20/25 |
20/25 |
|
Degree of Protection * |
|
IP4X |
IP4X |
IP4X |
| Auxiliary Operating Supply |
125/110/48/30V dc |
| Typical Weight Range |
500 - 650kg |
| Busbars |
1250A, 2000A |
Normal Service Conditions:
| Ambient air temperature |
-5ºC to +40ºC |
| Relative humidity |
<95% |
| Altitude |
<1000m |
Standards:
- IEC 62271-200, IEC 62271-100, IEC62271-102, IEC 62271-1
- ENA TS 41-36