NDCD Disconnector Ratings

NDCD Disconnector Ratings

Lightning NDCD

Ratings

Category


 

Category 1 disconnector, off-load

Number of plates


 

1

Operation


 

Motor driven / Manual / Both

Rated Voltage

V dc

1800

Rated Service Current

A

2000 / 4000 / 6000 / 8000

Rated Insulation Voltage

V dc

3000

Rated Impulse Withstand to Earth

kV

20

Rated Impulse Withstand across Isolating Distance

kV

24

Power Frequency Withstand to Earth

kV

9.2

Rated Impulse Withstand across Isolating Distance

kV

11

Rated Auxiliary Supply Voltage

V dc

110

Rated Short-Time Withstand Current

kA

180 peak (125 steady state)

Standard Auxiliary Contact(s) (more available on request)


 

1n/o 1n/c at each position(s)